SAGEMCOM 252720938AB工控控制卡件
這些參數(shù)用于設(shè)置CI854/CI854A。通常,大多數(shù)參數(shù)無需更改。標(biāo)有*的參數(shù)將由Control Builder計(jì)算(在下載期間),但可能需要調(diào)整,因?yàn)槭褂昧颂厥獾膹脑O(shè)備、中繼器或段耦合器。端地址這是主設(shè)備的PROFIBUS地址,范圍可以在1-125之間。此地址必須與所有其他從屬地址不同,否則會(huì)生成編譯錯(cuò)誤。根據(jù)配置中的設(shè)備編號為從屬設(shè)備分配地址。使用多主系統(tǒng),確保與其他主系統(tǒng)及其從屬系統(tǒng)之間沒有尋址沖突。波特率支持的波特率為9.6;19.2; 93.75; 187.5; 500; 1500; 3000; 6000和12000千比特/秒。不支持波特率31.25和45.45 kbit/s。默認(rèn)值為1.5 Mbit/s。較高的值需要仔細(xì)考慮正確的電纜安裝。所有從屬設(shè)備必須支持波特率設(shè)置。某些從設(shè)備在波特率更改后需要手動(dòng)復(fù)位。
These parameters are used to set up CI854/CI854A. Normally, most of the
parameters need not be changed. Parameters marked with a * will be calculated (during download) by the Control Builder, but may need to be adjusted due to
special slaves, repeaters, or segment couplers used.ode address This is the PROFIBUS address of the master which can be in the
range 1-125. This address must differ from all other slave
addresses, otherwise a compilation error is generated. Slaves are
assigned their addresses according to the device numbering in the
configuration. With multi-master systems ensure that there is no
addressing conflict with the other masters and their slaves.
Baudrate Supported baudrates are 9.6; 19.2; 93.75; 187.5; 500; 1500; 3000;
6000 and 12000 kbit/s. Not support are the baud rates 31.25 and
45.45 kbit/s. The default value is 1.5 Mbit/s. Higher values require
careful consideration of correct cable installation. All slave devices
must support baud rate setting. Some slaves require a manual
reset after change of the baud rate.