YAMATAKE EST0240Z05WBX00觸摸顯示屏工控
用Control Builder M配置的位置必須符合硬件單元本身配置的PROFIBUS地址。硬件單元上的配置通常通過DIP開關(guān)完成。如果裝置沒有像PROFIBUS PA設(shè)備一樣的DIP開關(guān),則可以使用第77.3頁(yè)SetAddress中描述的Web界面通過PROFIBUS設(shè)置其地址。如果模塊應(yīng)設(shè)置為冗余,請(qǐng)選中啟用冗余模式。備份從屬設(shè)備的位置將自動(dòng)計(jì)算并顯示(另請(qǐng)參閱第28頁(yè)的從屬冗余)。4.單擊“插入”按鈕應(yīng)用當(dāng)前更改。5.單擊“關(guān)閉”關(guān)閉對(duì)話框或繼續(xù)插入更多單元。硬件單元現(xiàn)在包含在樹中。樹中顯示的圖標(biāo)取決于是否配置了冗余。對(duì)于冗余配置單元,備份模塊的位置顯示在括號(hào)內(nèi)。如果FCI應(yīng)在冗余模式下工作,則需要在硬件的設(shè)置選項(xiàng)卡中配置冗余
The position configured with Control Builder M has to fit to the PROFIBUS
address configured on the hardware unit itself. The configuration on the hardware
unit is typically done via DIP switches. If the unit does not have a DIP switch like
a PROFIBUS PA device it is possible to set its address via the PROFIBUS using
the Web interface described in SetAddress on page 77.3. If the module shall be set redundant check Enable redundant mode. The
position for the backup slave will be calculated automatically and displayed
(see also Slave Redundancy on page 28).
4. Click Insert button to apply the current changes.
5. Click Close to close the dialog or proceed inserting further units.The hardware unit is now included in the tree. The icon shown in the tree
depends on if redundancy is configured or not. For a redundant configured unit
the position for the backup module is presented within parenthesis.If the FCI shall work in redundant mode, it is needed to configure redundancy in
the settings tab of the hardware